小型制藥冷凍干燥機日常維護和保養!
Check Before Running: 每次開機前要例行檢查
ü The state of various valves (absorbing, exhausting valves for compressors, service valves, capped valves and etc.)
所有截止閥(壓縮機吸、排氣閥、供液閥、手閥等)處于開啟狀態;
ü Pressure meter: 0.6~0.7Mpa
壓力表正常讀數:0.6~0.7Mpa
ü Level of compressor oil: 1/4~3/4
壓縮機正常油位:1/4~3/4;
After Power Supply, Please Notice: 送電后應注意
ü Whether compressor collects the refrigerant
壓縮機是否自動收液;
ü Whether difference-oil pressure resets
油壓差是否復位等;
After Running, Please Notice: 開機后注意
ü Whether the sound of compressor is normal, if not, please check power supply
壓縮機運行聲音是否正常,如果異常請先檢查供電的三相電是否平衡;
ü Whether the refrigerating piping vibrates normally, if yes, please fix the loosen parts
制冷管路是否有異常振動,如果有則采用相應的固定措施;
ü Whether the flux of refrigerant is normal by observing the sight glass, if having bubble in sight glass, please check the content of refrigerant and thermostatic valves
視液鏡流量是否正常,若有氣泡,則說明制冷劑缺少或膨脹閥流量太大;
ü The state of frosting on the thermostatic valves
膨脹閥結霜情況;
ü The state of frosting on the compressor
壓縮機回霜情況;
ü Compressor oil return, generally, 1/3~3/4
冷凍油的回油情況;(一般保持在油視鏡的1/3~3/4)
Compressor Start-up: 壓縮機啟動
ü Start frequently as little as possible, internal more than 3min
不能頻繁啟動,間隔的時間應大于3min;